| Attachment Name |
Rated control power supply
Voltage Ue |
Trip voltage |
Function |
|
Overvoltage trip unit
MV(iMSU)
|
AC230V |
Overvoltage value :270V±5% |
When the power supply voltage rises to 270V±5%, the circuit breaker is tripped to achieve overvoltage protection for the circuit. |
Under-voltage trip unit MN(iMN) |
AC230V |
Under-voltage value :<160V±5% |
When the power supply voltage drops below 160V, the circuit breaker is tripped to achieve undervoltage protection for the circuit. |
Overvoltage and undervoltage trip unit MV+M N(iMNV) |
AC230V |
Overvoltage value :270V±5% Under-voltage value :<160V±5% |
When the power supply voltage rises to 270V±5% or drops below 160V, the circuit breaker is tripped to achieve line protection. |
| Three-phase overvoltage and undervoltage + phase loss MV+MN (iMNV) |
AC380V |
Overvoltage value :460V±15V
Under-voltage value :300V±15V
|
When the power supply voltage rises to 460V±15V or drops below 300V±15V, the circuit breaker is tripped to achieve line protection. |
| Three-phase four-wire overvoltage and undervoltage MV+MN(iMNV) |
AC230V |
Overvoltage value :270V±5V Undervoltage value:<160V±5% |
When the power supply voltage rises to 270V±5V or drops below 160V±5V, the circuit breaker trips to achieve line protection. |
| Electronic undervoltage trip unit MNS (iMNS) |
AC230V |
Under-voltage value :170V±5% Undervoltage value :0 tripping |
When the power supply voltage drops to 170V±5% or there is no electricity, the circuit breaker trips to achieve undervoltage protection of the line (the circuit can be closed during power failure). |
| Electromagnetic undervoltage trip unit MNS (iMNS) |
AC230V |
Under-voltage value :35% to 75% Undervoltage value :0 tripping |
When the power supply voltage drops to 35% to 75% or there is no electricity, the circuit breaker trips to achieve undervoltage protection of the line (the circuit cannot be closed during a power outage). |
| Electromagnetic undervoltage trip unit MNS (iMNS)(For photovoltaic use) |
AC230V |
Under-voltage value :35% to 75% Undervoltage value :0 trip (with delay) |
When the power supply voltage drops to 35% to 75% or there is no electricity, the circuit breaker (delayed) trips to achieve undervoltage protection of the line (the circuit cannot be closed during power failure). |
|
Electromagnetic overvoltage and undervoltage tripping
Instrument MNVS(iMNVS
(For photovoltaic use)
|
AC230V |
Overvoltage value :270V±5% Under-voltage value :35% to 75% Undervoltage value :0 trip (with delay) |
When the power supply voltage rises to 270V±5V or drops to 35% - 75% or there is no electricity, the circuit breaker (delayed) trips to achieve overvoltage and undervoltage undervoltage protection of the line (the circuit cannot be closed during power failure). |